Skip to the main content
The Crier

Biodiesel Pump

Your saved contracts

What the buyer wrote

The supplier should be able to provide a biodiesel pump and install it at the CHP engine room located in the EBRI Plant. An electrically driven Atex rated self-priming pump is to be installed for un-supervised operation to run a CHP engine. The pump is to fill a 100 litre biodiesel stainless steel day tank, from a plastic IBC tank where the biodiesel is stored. The pump must be controlled by a level sensor in the day tank to avoid overfilling, and a level sensor in the IBC tank to avoid pumping air. The pump and its ancillaries such as sensors, piping and seals must be rated for biodiesel B100 EN14214. Additional information: PLEASE SEE THE FOLLOWING LINK TO VIEW THE FULL TECH…

Read all of it on Contracts Finder →

Details

What the buyer calls it
Biodiesel Pump
How they are buying
Advertised, open to anyoneAny supplier could bid without being invited first.
Type
goods
Suitable for small firms
The buyer says yes. What that is worth
Work starts
1 Apr 2015
Work ends
1 Jul 2015

Who the buyer named

Jason Goodwin was the named contact on this notice.

j.goodwin@aston.ac.uk