Main LV to Sub Main Feed Cable Replacement
What the buyer wrote
The existing cables are over 20 years old and have been subject to degradation due temperature variations through power loading and the local environment, currently the feed cable to FCS sub main panel failed an insulation resistance test with a reading of 800K Ohms, this reading fluctuates between 800k Ohms and 1.2 M Ohms . The pass level is 1 M-Ohm, we are experiencing these readings on testing other main feed cables, so a programme of replacement is required.
Details
- What the buyer calls it
- Main LV to Sub Main Feed Cable Replacement
- How they are buying
- The buyer did not say
- Type
- works
- Suitable for small firms
- The buyer says yes. What that is worth
- Work starts
- 12 Jun 2016
- Work ends
- 30 Jun 2018
Who the buyer named
Rene Kiliaan was the named contact on this notice.