What the buyer wrote

The existing cables are over 20 years old and have been subject to degradation due temperature variations through power loading and the local environment, currently the feed cable to FCS sub main panel failed an insulation resistance test with a reading of 800K Ohms, this reading fluctuates between 800k Ohms and 1.2 M Ohms . The pass level is 1 M-Ohm, we are experiencing these readings on testing other main feed cables (chilled water feed cables) (north main feed cable) (BSD main and HVac feed cables) so a programme of replacement is required.

Bid for this and lost? There is a short window in which the decision can be questioned.

Awarded to

Bowers Projects Limited£549.1kends (1 Jul 2018)